First time here? Check out the Help page!
1 | initial version |
The descriptions of what each variable means are listed in the Input Output Reference documentation.
The variables you mention are outputs from ElectricLoadCenter:Distribution
(docs).
Facility Total Building Electric Demand Power [W]
This output variable includes all of the electric demand from the building (non-HVAC) portion of the simulation, which would contain lights, electrical equipment, exterior lights and equipment, etc. Facility
Total HVAC Electric Demand Power [W]
This output variable includes all of the electric demand from the HVAC portion of the simulation, which would contain fans, electric coils, pumps, chillers, cooling towers, etc.
Facility Total Electric Demand Power[W]
This is the total of the whole Building and HVAC electric demands.
2 | No.2 Revision |
The descriptions of what each variable means are listed in the Input Output Reference documentation.
The variables you mention are outputs from ElectricLoadCenter:Distribution
(docs).
Facility Total Building Electric Demand Power [W]
This output variable includes all of the electric demand from the building (non-HVAC) portion of the simulation, which would contain lights, electrical equipment, exterior lights and equipment,
etc. Facilityetc.Facility Total HVAC Electric Demand Power [W]
This output variable includes all of the electric demand from the HVAC portion of the simulation, which would contain fans, electric coils, pumps, chillers, cooling towers, etc.
Facility Total Electric Demand Power[W]
This is the total of the whole Building and HVAC electric demands.
3 | No.3 Revision |
The descriptions of what each variable means are listed in the Input Output Reference documentation.
The variables you mention are outputs from ElectricLoadCenter:Distribution
(docs).
Facility Total Building Electric Demand Power [W]
This output variable includes all of the electric demand from the building (non-HVAC) portion of the simulation, which would contain lights, electrical equipment, exterior lights and equipment, etc.
Facility Total HVAC Electric Demand Power [W]
This output variable includes all of the electric demand from the HVAC portion of the simulation, which would contain fans, electric coils, pumps, chillers, cooling towers, etc.
Facility Total Electric Demand
Power[W]Power [W]This is the total of the whole Building and HVAC electric demands.