In the Ventilation Type
field if you set it to Exhaust
or Intake
, the assumption is that there is a fan drivingthe flow which requires you to enter the Pressure Rise
and Fan Efficiency
. Balanced
is a combination of Intake and Exhaust so you also need to enter those two fields for that selection too. If you set it to Natural
there is not assumed to be a fan and those fields are optional.
As an aside, the majority of questions related to objects and inter-workings can be answered by looking at the EnergyPlus Input Output Reference or Engineering Reference, always check there first.