It's been a while since you posted this, so maybe you figured it out already. But for the record, there are several things contributing to no heating load in many zones.
- GroundTemperatures are all 22C. This is quite warm.
- There is no infiltration.
- Lights and electric equipment are using normal weekday schedules for WinterDesignDay - suggest using the holiday day schedules for WinterDesignDay.
- Thermal Zone 10, for example, has no exterior surfaces, so I would not expect a design heating load for this zone.