It looks like you're using ZoneVentilation:DesignFlowRate
since you have no Mechanical Ventilation, but you do have Simple Ventilation. I believe that this is going to be reported as Infiltration in the Sensible Heat Gains Summary. That value being the largest is consistent with your Outdoor Air table since you have the highest total outdoor air ACH in that zone (0.982 vs 0.553 and 0.454). I could be wrong though, that's just a guess.