You can confirm that the reheat coils are connected by clicking on the reheat terminal, then the chain link icon in the upper right. Here is what correctly connected reheat coils look like:
If the reheat coils were not connected correctly, you'd probably be getting severe errors about node connection failures in the reheat coils. If your air terminals are not reheat terminals, they won't have the chain link icon at all, and you'll have found your problem.
If everything is connected correctly, then it's a controls problem. At that point, I'd probably check out the zone sizing temperatures vs. the reheat terminal heating air temperatures.