First time here? Check out the Help page!
1 | initial version |
The key to getting the plant to shut down is going to be to get all the chilled water demand devices to turn off and not be requesting any chilled water. Assuming you want the air handlers to continue running for heating and ventilation, I would try to use SetpointManager:OutdoorAirReset to increase the cooling coil setpoint (on a system air node) to something really high when outdoor air gets to 10.0C.