Would need more info to really determine what's going on. Could be a number of issues:

  • Sizing: 4000 W
    • s

Would need more info to really determine what's going on. Could be a number of issues:

  • Sizing:

    4000 W
    • s4000 W boiler capacity is too low, so boiler operates almost all the time
  • inlet and outlet temperature fields in Sizing:Plant, Boiler, and baseboard HW coil objects don't match
  • you autosized flow rate for boiler, but may have hard-set flow rate for baseboard heaters

Baseboard Heaters

  • UA calculations for coils may yield low heat transfer efficiency

My guess is that the last point is the culprit, but all are worth checking out.

Would need more info to really determine what's going on. Could be a number of issues:

Sizing:

  • 4000 W boiler capacity is too low, so boiler operates almost all the time
  • inlet and outlet temperature fields in Sizing:Plant, Boiler, and baseboard HW coil objects don't match
  • you autosized flow rate for boiler, but may have hard-set flow rate for baseboard heaters

Baseboard Heaters

  • UA calculations for coils may yield low heat transfer efficiency
  • Availability schedule for baseboard and/or HW coils limits time of operation

My guess is that the last point is baseboard inputs are the culprit, but all are worth checking out.