Would need more info to really determine what's going on. Could be a number of issues:

  • Sizing: 4000 W
    • s
click to hide/show revision 2
No.2 Revision

Would need more info to really determine what's going on. Could be a number of issues:

  • Sizing:

    4000 W
    • s4000 W boiler capacity is too low, so boiler operates almost all the time
  • inlet and outlet temperature fields in Sizing:Plant, Boiler, and baseboard HW coil objects don't match
  • you autosized flow rate for boiler, but may have hard-set flow rate for baseboard heaters

Baseboard Heaters

  • UA calculations for coils may yield low heat transfer efficiency

My guess is that the last point is the culprit, but all are worth checking out.

click to hide/show revision 3
No.3 Revision

Would need more info to really determine what's going on. Could be a number of issues:

Sizing:

  • 4000 W boiler capacity is too low, so boiler operates almost all the time
  • inlet and outlet temperature fields in Sizing:Plant, Boiler, and baseboard HW coil objects don't match
  • you autosized flow rate for boiler, but may have hard-set flow rate for baseboard heaters

Baseboard Heaters

  • UA calculations for coils may yield low heat transfer efficiency
  • Availability schedule for baseboard and/or HW coils limits time of operation

My guess is that the last point is baseboard inputs are the culprit, but all are worth checking out.