EnergyPlus v8.4.0 (Sept 2015) has a new feature to account for DOAS effects during sizing. Several new fields have been added to the Sizing:Zone object. From example file 5ZoneFanCoilDOASCool.idf
Sizing:Zone,
SPACE1-1, !- Zone or ZoneList Name <snip>
SZ DSZAD SPACE1-1, !- Design Specification Zone Air Distribution Object Name
Yes, !- Account for Dedicated Outside Air System
ColdSupplyAir, !- Dedicated Outside Air System Control Strategy
12.8, !- Dedicated Outside Air Low Setpoint for Design
15.6; !- Dedicated Outside Air High Setpoint for Design