I think you would have to use EMS. The PVT would need a dummy air handler connected to a dummy zone to get it to run. Then an EMS sensor on System Node Temperature would detect the temperature leaving the PVT and an EMS actuator would set the value of either a schedule value or an outdoor air node's temperature.