What I observed:
Zone Heating Design Supply Air Temperature
in Sizing:Zone
) - (Maximum Dry-Bulb Temperature
for WinterDesignDay
in SizingPeriod:DesignDay
)I don't think either is appropriate. The DX cooling coil capacity and the DX heating coil capacity do not have to be identical. They are different in the real world. Moreover, they are separate objects in EnergyPlus. The supplement heating coil capacity is excessively large due to the unreasonable assumption that all the supply air is fresh air. I'll post on github as bugs.