This is likely be an extra semi-colon on line 79649 of your IDF that precedes "Cooling Coil Electricity Energy" on line 79650 that the severe error message mentions.

For example, unless you have a copy/paste typo, replace

Meter:Custom,
  ...
  EL01SalesAHU03 PSZ-AC 1spd DX AC Clg Coil;     !- Key Name
  Air System DX Cooling Coil Electricity Energy;  !- Output Variable or Meter Name

with

Meter:Custom,
  ...
  EL01SalesAHU03 PSZ-AC 1spd DX AC Clg Coil,     !- Key Name
  Air System DX Cooling Coil Electricity Energy;  !- Output Variable or Meter Name

This is likely be an extra caused by a semi-colon ";" instead of a comma "," finishing the input field on line 79649 of your IDF that precedes "Cooling Coil Electricity Energy" on line 79650 that the severe error message mentions.

For example, unless you have a copy/paste typo, replace

Meter:Custom,
  ...
  EL01SalesAHU03 PSZ-AC 1spd DX AC Clg Coil;     !- Key Name
  Air System DX Cooling Coil Electricity Energy;  !- Output Variable or Meter Name

with

Meter:Custom,
  ...
  EL01SalesAHU03 PSZ-AC 1spd DX AC Clg Coil,     !- Key Name
  Air System DX Cooling Coil Electricity Energy;  !- Output Variable or Meter Name