The table Equipment Summary / For Facility / Chillers should list both Reference and Rated Temperatures (Entering Condenser Temperature, Leaving Evaporator Temperature). The Reference Temperatures are inputs in the Chiller:Electric:EIR object. If the Reference temps are the same as the Rated temps, the Reference Capacity will be equivalent to the Rated Capacity. If the temperatures are different, the rated/ref capacities will be different.